KUALITAS PENGOLAHAN AIR LIMBAH RUMAH SAKIT UMUM DI PROVINSI KALIMANTAN SELATAN TAHUN 2020

Detail Cantuman

CD-ROM

KUALITAS PENGOLAHAN AIR LIMBAH RUMAH SAKIT UMUM DI PROVINSI KALIMANTAN SELATAN TAHUN 2020

XML

KEMENENTERIAN KESEHATAN REPUBLIK INDONESIA
POLITEKNIK KESEHATAN BANJARMASIN
PROGRAM STUDI SANITASI
PROGRAM DIPLOMA III
KESEHATAN LINGKUNGAN
TAHUN 2020
ABSTRAK
Karya Tulis Ilmiah
MISNAWATI NURHASANAH
“KUALITAS PENGOLAHAN AIR LIMBAH RUMAH SAKIT UMUM DI PROVINSI KALIMANTAN SELATAN”
(Munawar Raharja, S.Si, M.PH; Dr. Abdul Khair, S.KM, M. Si)
xvi + 51 halaman + 11 tabel + 1 gambar + 13 lampiran
Rumah sakit sebagai salah satu pusat pelayanan kesehatan, yang berpotensi menghasilkan bahan-bahan yang bersifat infeksius dan non infeksius, yang dapat menurunkan kualitas lingkungan dan gangguan kesehatan. Penelitian ini bertujuan mengetahui kinerja Instalasi Pengolahan Air Limbah Rumah Sakit Umum di Provinsi Kalimantan Selatan.
Penelitian ini merupakan penelitian yang bersifat deskriptif dengan desain Cross Sectional. Populasi dalam penelitian ini adalah semua air limbah yang dihasilkan, dengan sampel sebagian yang dapat mewakili terkait pengolahan air limbah, pengambilan sampel menggunakan metode composite sampling dengan pengambilan sampel 3 kali pada pukul 08.00 WITA, 12.00 WITA, 16.00 WITA dan 2 kali pengulangan. Penelitian ini bertujuan untuk mengetahui kualitas pengolahan air limbah Rumah Sakit Umum di Provinsi Kalimantan Selatan.
Hasil dalam penelitian menunjukkan rata-rata volume air limbah adalah 71.400 liter/hari, pada influent rata-rata pH 7,7; suhu 28°C; TSS 12,5 mg/L; BOD 8 mg/L; COD 54,15 mg/L; NH3 bebas 0,08 mg/L; Colliform 107.000 MPN/100ml dan pada kualitas effluent rata-rata pH 7,2; suhu 27°C; TSS 9,5 mg/L; BOD 3,85 mg/L; COD 21,6 mg/L; NH3 bebas 0,07 mg/L; Colliform 81.000 MPN/100ml untuk efektivitas pada IPAL mampu menurunkan kadar TSS 24%; BOD 51,8%; COD 60,1%; NH3 bebas 12,5%; dan Colliform 24,3%.
Upaya yang dapat dilakukan adalah melakukan perawatan dan pemeriksaan secara berkala pada IPAL, mengoperasikan secara kontinyu terhadap unit reaktor oksidasi.

Kata kunci : IPAL, Air Limbah, Rumah Sakit
Kepustakaan : 24 (2006 – 2019)


MINISTRY OF HEALTH REPUBLIC OF INDONESIA
HEALTH POLYTECHNIC OF BANJARBARU
ENVIRONMENTAL SANITATION PROGRAM
STUDY PROGRAM DIPLOMA III
ENVIROMENTAL HEALTH
YEAR 2020

ABSTRACT

Scientific Paper
MISNAWATI NURHASANAH
QUALITY OF PUBLIC HOSPITAL WASTEWATER TREATMENT IN SOUTH KALIMANTAN PROVINCE
(Munawar Raharja, S.Si, M.PH; Dr. Abdul Khair, S.KM, M. Si)
xvi + 51 Pages + 11 Tables + 1 Pictures + 13 Attachments
Hospital waste water is one of worst pollutions which could be have bad Hospital is one of health care centers that potentially produce infectious and non-infectious wastes, which have possibility to decrease the environment and health quality. This research aimed to find out the process of Waste Water Treatment Plant in of Waste Water Treatment Plant in South Kalimantan Province through observation, intervews, and measurement according to the Ministry of Environment Regulation Number 5/2014.
This research is a descriptive study, the population in this study is all the effluent water produced, with a partial sample that can represent related wastewater treatment, sampling using composute sampling method with 3 times sampling at 08.00 WITA, 12.00 WITA, 16.00 WITA and 2 times repetition. This research aims to determine the source, volume, quality of influent and effluent and the affectiveness of sewage treatment.
The results showed that usually there are 18.864liters waste water every day, the process of WWTP included pre-treatment, processing phase, and after-processing phase. The results also showed the numbers of influent quality consist of: 7.7 pH; 28°C temperature; 12,5 mgs/L TSS; 8 mgs/L BOD; 54,15 mgs/L COD; 0.08 mgs/L NH3 free and 107.000 Colliform. In effluent quality: 7,2 pH; 27°C temperature; 9,5 mgs/L TSS; 3,85 mgs/L BOD; 21,6 mgs/L COD; 0.07 mgs/L NH3 free and 81.000 Colliform; the WWTP in the other hand, could decrease about 24% number of TSS, 51,8% of BOD; 60,1% of COD; and 12,5% of NH3 free and 24,3% of Colliform..
The effort is to perform periodic maintenance and inspection of the IPAL, operating continuously against the oxidation reactor units

Keywords: Hospital, Waste Water Treatment Plant, Waste water
Libraries : 24 (2006-2019)


Detail Information

Item Type
Penulis
MISNAWATI NURHASANAH - Personal Name
Munawar Raharja, S.Si, M.PH - Personal Name
ABDUL HARIS - Personal Name
Student ID
Dosen Pembimbing
Penguji
Kode Prodi PDDIKTI
Edisi
Departement
Kontributor
Bahasa
Indonesia
Penerbit : Banjarbaru.,
Edisi
Subyek
No Panggil
KL.22/KTI.2020
Copyright
Doi

Lampiran Berkas

LOADING LIST...



Informasi


DETAIL CANTUMAN


Kembali ke sebelumnya  XML Detail